Viessmann · Mini-split troubleshooting

How to read the D5CSRA cooling performance matrices

D5CSRA

What is going on

Pages 64 to 72 hold cooling capacity matrices for the D5CSRA with different indoor units (the table titles on these pages cover 18K 4-way cassette and 9K AE console). Each block is one outdoor-air temperature (DB) row, from -22°F (-30°C) up to 122°F (50°C). Each row gives three values per indoor-air condition: TC (total cooling capacity), S/T (sensible-to-total heat ratio) and PI (power input). Values are grouped by indoor wet-bulb (ID WB) and indoor dry-bulb (ID DB) columns, and each table is labelled with one airflow in CFM.

Check in this order

  1. Find the table for the indoor unit type and capacity size (9K, 12K, 18K, 24K and so on) by its title.
  2. Note the airflow in CFM printed above the block and pick the matching airflow.
  3. Select the outdoor DB row that matches the outdoor air temperature on site.
  4. Read across to the indoor WB and DB column that matches the room conditions.
  5. Read TC for capacity, S/T for the sensible share, and PI for the electrical input at those conditions.
  6. Use the note in the table heading for any capacity table that continues onto the next page.

Applies to: D5CSRA outdoor units with indoor units: 4-way cassette, AE console, and similar cooling tables on pages 64 to 72

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5CSRA Product Data, p. 64-72. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.