Viessmann · Mini-split troubleshooting
Hanging the indoor unit in the ceiling
What is going on
Cut the ceiling opening and hang the unit on four suspension bolts. The unit must match the hole size before continuing.
Check in this order
- Use the paper template to cut a rectangular hole, leaving at least 39 in. (1 m) clearance on all sides.
- Make the hole 1.6 in. (4 cm) larger than the unit body on each side.
- Mark the ceiling hook drill positions.
- Drill 4 holes 4.7 to 6.1 in. (12 to 15.5 cm) deep at 90 degrees to the ceiling.
- Fix the ceiling hooks in the holes with the washers and nuts.
- Install four suspension bolts, either M8 or M10.
- Check that the unit body aligns with the hole and that the sizes match before proceeding.
Applies to: Cassette indoor unit installation
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLFSCBH and DLFLCBH installation instructions, p. 7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.