Viessmann · Mini-split troubleshooting

Hang the indoor unit on the mounting plate

DLFSHC

What is going on

Hook the unit on the plate and confirm it is secure before the pipe work is finished.

Check in this order

  1. Pass the wrapped bundle through the wall hole.
  2. Hook the top of the indoor unit onto the upper hook of the mounting plate.
  3. Push on the sides of the unit to check it is firmly hooked and does not jiggle.
  4. Press evenly on the bottom half until the unit snaps onto the lower hooks.
  5. Check again for firm mounting on both sides.
  6. If there is not enough room to connect the embedded pipe, shift the unit left or right by 1.18-1.95 in (30-50 mm), depending on the model.

Applies to: DLFSHC indoor units

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSHC installation instructions, p. 14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.