Flare connection for interconnecting piping

Vitocal IND-F

What is going on

Cut, deburr and flare the copper line, then torque the flare nut to the value in the table. Use refrigerant oil on the flare seat.

Check in this order

  1. Cut the pipe square at 90 degrees with a pipe cutter.
  2. Remove all burrs from the cut edge, including inside the tube.
  3. Remove the flare nuts from the indoor and outdoor unit connections.
  4. Slide a flare nut onto the pipe and flare it to the dimensions in Table 4.
  5. Apply a small amount of refrigerant oil to the flare seat.
  6. Align the center of the two pipes.
  7. Connect the liquid and gas lines to the indoor unit.
  8. Tighten the flare nut with a torque wrench to the value in Table 5.

Applies to: All sizes

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSFA and DLFLFA installation instructions, p. 10-11. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.