Viessmann · Mini-split troubleshooting
Field wiring installation checks (indoor to outdoor unit)
What is going on
Checks to make before energising the indoor and outdoor units. Power and communication run between the two units in one cable set.
Likely causes
- Loose terminals can overheat and cause unit malfunction or a fire hazard.
- Communication problems can come from electromagnetic interference in high EMF areas.
Check in this order
- Size all wires per NEC or CEC and local codes, using the MCA and MOCP values from the electrical data table.
- Use field supplied 14/3 stranded wire with ground, 600 V rated, for the power and communication run.
- Keep the four conductors correct two line voltage, one communication (S) and one ground.
- Keep polarity correct on the indoor to outdoor wiring, as it is polarity sensitive.
- Do not use BX cable.
- In a high EMF area with communication problems, use 14/2 stranded shielded wire for L2 and S and ground the shield at the outdoor unit only.
- Tighten every wire connection.
- Route no wire against refrigerant tubing, the compressor or any moving part.
- Provide a disconnect within sight of, and readily accessible from, the unit.
Applies to: DLFSCBH and DLFLCBH, sizes 24K, 36K, 48K
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal IND-C technical data manual, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.