Viessmann · Mini-split troubleshooting
Field wiring between outdoor and indoor units
What is going on
Power and communication wires run between the outdoor and indoor units. Wire size depends on the unit size. Wire must be sized to NEC/CEC and local codes using outdoor unit MCA and MOCP.
Likely causes
- Loose terminations can overheat or cause malfunction
- Wire touching refrigerant tubing, compressor or moving parts
Check in this order
- Size all wires per NEC or CEC and local codes using outdoor MCA and MOCP.
- Sizes 09 to 24 run four conductors (two AC power, one communication, one ground) using 14/3 power and communication wire.
- If EMF interference occurs on sizes 09 to 24, use 14/2 stranded shielded wire in place of L2 and S, grounding the shield at the outdoor unit only.
- Sizes 36 to 58 run three power conductors (two AC power and one ground), 14/2 stranded with ground recommended.
- Sizes 36 to 58 run a separate shielded stranded copper communication wire, 600 V rated, 16 GA stranded control wire.
- Tighten every connection; check no wire touches refrigerant tubing, compressor or moving parts.
- Install a disconnect within sight and readily accessible from the system.
Applies to: Sizes 09 to 58
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann DLFSDAH & DLFLDAH Technical Data Manual, pp. 10 and 11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.