Viessmann · Mini-split troubleshooting
Evaporator low temperature protection (T2)
What is going on
The compressor is limited or stopped when the evaporator pipe temperature (T2) is low.
Likely causes
- T2 below 32 °F (0 °C)
- T2 between 32 and 39.2 °F (0 to 4 °C)
Check in this order
- If T2 is below 32 °F (0 °C), the compressor stops and restarts when T2 reaches 41 °F (5 °C).
- If T2 is 32 to 39.2 °F (0 to 4 °C), the compressor frequency is reduced to a lower level.
- If T2 is 39.2 to 44.6 °F (4 to 7 °C), the compressor holds its current frequency.
- If T2 is above 44.6 °F (7 °C), the compressor frequency is not limited.
Applies to: Evaporator temperature sensor T2, DLFSFBH 12K
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.