Viessmann · Mini-split troubleshooting

Evaporator low temperature protection (T2)

Vitocal IND-F

What is going on

The compressor is limited or stopped when the evaporator pipe temperature (T2) is low.

Likely causes

  • T2 below 32 °F (0 °C)
  • T2 between 32 and 39.2 °F (0 to 4 °C)

Check in this order

  1. If T2 is below 32 °F (0 °C), the compressor stops and restarts when T2 reaches 41 °F (5 °C).
  2. If T2 is 32 to 39.2 °F (0 to 4 °C), the compressor frequency is reduced to a lower level.
  3. If T2 is 39.2 to 44.6 °F (4 to 7 °C), the compressor holds its current frequency.
  4. If T2 is above 44.6 °F (7 °C), the compressor frequency is not limited.

Applies to: Evaporator temperature sensor T2, DLFSFBH 12K

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.