Viessmann · Mini-split troubleshooting

Electrical parts removal, sizes 48K-58K

VITOCAL 100-S

What is going on

Steps to disconnect power and ground wires, remove the main control board and fan motor capacitors. Connections noted on the diagram: low and high pressure switch, T3 and T4, TP to indoor unit, and wires from the main board to the IPM module board.

Check in this order

  1. Remove the 2 screws to disconnect the power supply wires.
  2. Remove the 3 screws to disconnect the ground wires.
  3. Disconnect the wires connected to the main control board.
  4. Disconnect the wires between the main control board and the IPM module board.
  5. Remove the 4 screws and loosen the 6 hooks, then remove the main control board.
  6. Remove 1 screw per fan motor capacitor, then remove the capacitor.

Applies to: DLCLRC outdoor unit, sizes 48K and 58K (Models 48AAK, 58AAK)

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLCLRC service manual, p. 47. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.