Viessmann · Mini-split troubleshooting
Electrical control box removal (18K Standard Heat)
What is going on
Removes the electronic control box subassembly. Wear anti-static gloves when handling the electronic box. The box cover cannot be removed on this model, so P to N voltage cannot be measured.
Check in this order
- Turn off power and wear anti-static gloves.
- Disconnect the compressor connector.
- Release the ground wire (one screw).
- Remove the electronic control box subassembly.
Applies to: Model 18K Standard Heat
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLCURA service manual, p. 67 of 84. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.