Viessmann · Mini-split troubleshooting

Drill the wall hole for connecting piping

DLFSHC

What is going on

The wall hole must slope down to the outside so condensate drains properly.

Check in this order

  1. Find the wall hole position from the mounting plate dimensions and the figures for the unit size.
  2. Drill with a 2.5 in (65 mm) core drill, or a 3.54 in (90 mm) core drill if the gas line is 5/8 in (16 mm) or larger.
  3. Drill slightly downward so the outside end is about 0.2-0.275 in (5-7 mm) lower than the inside end.
  4. Fit the protective wall cuff in the hole.

Applies to: DLFSHC indoor units

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSHC installation instructions, p. 10-11. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.