Viessmann · Mini-split troubleshooting
Distorted or unrecognised indoor display
What is going on
Display shows a distorted code, a code not in the manual, or a value that is not a temperature reading.
Applies to: Indoor unit display board
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 14. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.