Viessmann · Mini-split troubleshooting
Display shows a strange code or does not answer the remote - DLFSHB indoor
What is going on
Viessmann DLFSHB high wall indoor, 09-24K. Display shows an odd code not in the tables, or the unit ignores the remote. Check what the display is really showing before blaming a board.
Likely causes
- Temperature reading mistaken for a code
- Bad indoor PCB
- Bad display board
Check in this order
- Make sure the code is not just a temperature reading.
- Test with the remote. Display works but the unit ignores the remote, replace the indoor PCB.
- Unit responds but the display stays dark after pressing LED, replace the display board.
- Power off and reseat the board connectors before condemning anything.
- Test again with fresh remote batteries to rule out the remote itself
Applies to: DLFSHBH high wall indoor units 09-24K (Midea / Carrier / Viessmann) on DLC multi-zone or single-zone outdoor units
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier MS-DLFSHB-01 High Wall Ductless Service Manual (04/2021), Table 9 notes p.17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.