DC fan motor test (indoor and outdoor)
What is going on
Checks whether the fault is in the fan motor or in the PCB.
Check in this order
- Indoor power on, put the unit in STANDBY, and measure voltage at the fan motor connector pin1-pin3 and pin4-pin3. Compare with the signal table.
- Indoor if the voltage is out of range, the PCB has failed; replace it.
- Outdoor shut off power, release the UVW connector, and measure resistance U-V, U-W and V-W.
- Outdoor if the three resistances are not equal, replace the fan motor.
- Outdoor if the three resistances are equal, replace the outdoor PCB.
Applies to: DLFSOAH 09XAK / 18XAK
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLFSOAH Service Manual, p. 19-20. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.