Connect and route the drain hose

DLFSHC

What is going on

The drain must slope and be free of kinks and traps so condensate runs out freely.

Check in this order

  1. Attach the drain hose to the same side the refrigerant piping exits the unit. The default is the left side when facing the back.
  2. Attach a drain hose extension if needed, and seal the connection with Teflon tape.
  3. Insulate the indoor portion of the drain hose with foam pipe insulation.
  4. Plug the unused drain hole with the supplied rubber plug.
  5. Route the hose with no kinks or dents and no low points that trap water.
  6. Do not place the hose end in water or in a container that collects water.
  7. Remove the air filter and pour a small amount of water into the drain pan to confirm flow.
  8. Use a field-supplied condensate pump if gravity drainage is not possible, and follow the pump instructions.

Applies to: DLFSHC indoor units

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSHC installation instructions, p. 12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.