Viessmann · Mini-split troubleshooting
Communication line DC voltage check (indoor to outdoor)
What is going on
Used with EL 01 to check the signal between the indoor and outdoor units.
Check in this order
- Use a multimeter on DC volts.
- Measure between the 2 port (or S or L2) and the 3 port (or N or S) of the outdoor unit. Red probe on the 2 port (or S or L2), black probe on the 3 port (or N or S).
- With the unit running normally, the reading swings between positive and negative values.
- If the reading is always positive, suspect the outdoor unit.
- If the reading stays at a fixed value, suspect the indoor unit.
- Check the reactor by measuring its resistance without the capacitor connected; it should be close to 0 ohm. Replace it if not.
Applies to: DLFSOAH 09XAK / 18XAK
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLFSOAH Service Manual, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.