Viessmann · Mini-split troubleshooting
Communication line DC voltage and reactor check
What is going on
Used with EL 01 to decide whether the indoor or outdoor side has failed.
Likely causes
- Faulty outdoor PCB if the reading is always positive
- Faulty indoor side if the reading is fixed
- Faulty reactor if its resistance is not near zero
Check in this order
- Measure the DC voltage between the 2 port (or S or L2) and the 3 port (or N or S) of the outdoor unit. Red pin on 2 (or S or L2), black pin on 3 (or N or S).
- Normal operation the voltage alternates between positive and negative.
- If the voltage is always positive, the outdoor unit has a fault.
- If the voltage stays at a fixed value, the indoor unit has a fault.
- Disconnect the reactor from the capacitor and measure its resistance. A good reactor reads close to zero ohms. Replace it if not.
Applies to: Indoor and outdoor communication, EL 01
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLFSFBH Service Manual, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.