Communication line DC voltage and reactor check

Vitocal IND-F

What is going on

Used with EL 01 to decide whether the indoor or outdoor side has failed.

Likely causes

  • Faulty outdoor PCB if the reading is always positive
  • Faulty indoor side if the reading is fixed
  • Faulty reactor if its resistance is not near zero

Check in this order

  1. Measure the DC voltage between the 2 port (or S or L2) and the 3 port (or N or S) of the outdoor unit. Red pin on 2 (or S or L2), black pin on 3 (or N or S).
  2. Normal operation the voltage alternates between positive and negative.
  3. If the voltage is always positive, the outdoor unit has a fault.
  4. If the voltage stays at a fixed value, the indoor unit has a fault.
  5. Disconnect the reactor from the capacitor and measure its resistance. A good reactor reads close to zero ohms. Replace it if not.

Applies to: Indoor and outdoor communication, EL 01

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSFBH Service Manual, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.