Lifebreath · Hrv troubleshooting
Poor airflow from HRV
What is going on
Weak supply or exhaust air at the grilles. Usually something plugged or closed.
Likely causes
- 1/4 in (6 mm) bird screen on an outside hood plugged
- Dirty filters
- Core blocked
- Grilles closed or blocked by furniture
- Balancing dampers closed
- Low supply voltage
- Duct run too restrictive
- Speed set too low on the control
- Unit not balanced
Check in this order
- Kill power at the HRV disconnect before opening the unit. Some units have more than one power feed.
- Check both outside hoods first. Clear leaves, snow or frost off the mesh.
- Pull and wash the filters, then pull and wash the core.
- Walk the house and open any closed or blocked grilles.
- Check the balancing dampers are open and set.
- Turn the speed up on the wall control and see if flow comes back.
- Check the duct install for crushed or long flex runs.
- If still weak, have an electrician check supply voltage and rebalance the HRV airflows.
Applies to: Lifebreath RNC series HRV
More hrv guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Lifebreath RNC5-ES Homeowner's Guide (69-RNC5-OWNERS 012616), Troubleshooting, p. 14. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.