Lifebreath · Hrv troubleshooting
Bathroom timer does not bring HRV to high
What is going on
Pressing the 20/40/60 timer does nothing.
Likely causes
- Main control mode set to OFF (timers don't work then unless wired for it)
- Wireless 99-DET02 out of range (about 40 ft clear line)
- Timer battery low
- Repeater not linked
- Timer in lockout (99-DET01)
Check in this order
- Check the main control is on and not set to OFF.
- On a wireless timer, check the red battery light and change the battery if lit.
- Check the distance to the main control. Add or move a 99-RX02 repeater if it is out of range.
- On a wired 99-DET01, hold the select button 5 seconds to take it out of lockout.
Applies to: 99-DET01, 99-DET02 timers, 99-RX02 repeater
More hrv guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Lifebreath RNC5-ES Homeowner's Guide (69-RNC5-OWNERS 012616), Timers, p. 9-11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.