Lifebreath · Hrv troubleshooting

Dehumidistat does not work

RNC

What is going on

The HRV does not go to high speed when the house is humid.

Likely causes

  • Outdoor temperature above 15°C (59°F) for 24 h, so the auto disable shut the dehumidistat off
  • Dehumidistat set to OFF

Check in this order

  1. Check the outdoor temperature. Above 15°C (59°F) for a full day the control turns the dehumidistat off by itself. That is normal.
  2. It turns back on after 24 h below 15°C (59°F), or after the HRV is unplugged for 30 seconds.
  3. Check the setting on the control and set it to the level wanted.

Applies to: BC02, BC03, DXPL02 controls with dehumidistat

More hrv guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Lifebreath RNC5-ES Homeowner's Guide (69-RNC5-OWNERS 012616), How the Dehumidistat Works, p. 4; Troubleshooting, p. 14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.