Zero crossing detection error
What is going on
If the zero crossing signal interval is wrong for 240 seconds continuously, the unit stops and the LED shows the failure. The correct interval is 6 to 13 ms.
Likely causes
- Zero crossing signal interval outside 6 to 13 ms
Check in this order
- Check the power supply waveform and wiring to the zero crossing input.
- Confirm the signal interval is between 6 and 13 ms.
Applies to: DLCURA outdoor unit
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLCURA Service Manual, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.