4-way reversing valve check
What is going on
Checks the reversing valve voltage in cooling mode and the coil resistance with the power off.
Check in this order
- Power on the unit and use a digital tester to measure the voltage while the unit runs in COOLING mode.
- Confirm the voltage reads 0 V. If it does not, replace the PCB.
- Turn off the power.
- Measure the coil resistance with a digital tester.
- Expected reading is 1.8 to 2.5 k (printed as KW on the page). Replace the valve coil if it is out of range.
Applies to: DLCSRB outdoor units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLCSRB Service Manual, p. 51. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.