Buried refrigerant line length and rise limits
What is going on
Buried refrigerant pipe must stay within the maximum buried length. Without the required vertical rise, refrigerant can migrate to the cold buried section while the system is off.
Likely causes
- Buried refrigerant pipe longer than 36 in.
- No vertical rise at the buried section to the outdoor unit valve connections
- Refrigerant migrating to the cold buried section during long shutdowns
Check in this order
- Limit buried refrigerant pipe to 36 in. (914 mm) maximum.
- If any pipe is buried, provide a 6 in. (152 mm) vertical rise to the outdoor unit valve connections.
- Check for refrigerant slugging and compressor damage at start-up if the limits were exceeded.
Applies to: DLCSRB outdoor units, sizes 06 to 36
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLCSRB Service Manual, p. 2. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.