Auto Changeover wiring and thermostat setup

Vitocal 100-AW AM2V

What is going on

With Auto Changeover, the thermostat sets heating or cooling mode through the changeover relay on FN2; the indoor unit dial only turns the system on or to standby.

Check in this order

  1. Wire the field-supplied thermostat to the changeover relay on FN2.
  2. On the thermostat, select heat pump mode.
  3. Set the thermostat O/B setting to cooling.
  4. Keep the FN1 contact closed for normal operation; opening it blocks operation.
  5. Check the relay light OFF means heating mode, ON means cooling mode.
  6. Check thermostat OFF behaviour, since it varies by thermostat (some default to heating, others keep the last mode).

Applies to: Vitocal 100-AW AM2V indoor unit with Auto Changeover

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-AW AM2V installation manual, p. 30. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.