Viessmann · Heat pump troubleshooting
A2L refrigerant leak mitigation check
What is going on
On a detected leak the compressor stops, the blower runs in continuous fan mode and the display shows GAS. Use this check to confirm the mitigation is working.
Likely causes
- A2L refrigerant leak detected
Check in this order
- Confirm GAS fault on the information display.
- Via terminal interface screen 1 LFL% should be above 15%, compressor percentage 0, fan above 10%.
- At the control board, confirm C1 and C2 are not sending 24VAC to the compressor start relay.
- At the start relay, confirm the coil is not energised and the 230V load side is not energised.
- At the compressor plug, confirm no amp draw on common, start or run wires.
- At the control board ECM terminal, confirm about 12VDC between G and C.
- At the blower high voltage connector, confirm amp draw on T1 and T2.
- Do not unplug the blower motor while it is running.
Applies to: Vitocal 100-WA with R-454B refrigerant
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 48. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.