Viessmann · Heat pump troubleshooting

A2L refrigerant leak mitigation check

Vitocal 100-WA

What is going on

On a detected leak the compressor stops, the blower runs in continuous fan mode and the display shows GAS. Use this check to confirm the mitigation is working.

Likely causes

  • A2L refrigerant leak detected

Check in this order

  1. Confirm GAS fault on the information display.
  2. Via terminal interface screen 1 LFL% should be above 15%, compressor percentage 0, fan above 10%.
  3. At the control board, confirm C1 and C2 are not sending 24VAC to the compressor start relay.
  4. At the start relay, confirm the coil is not energised and the 230V load side is not energised.
  5. At the compressor plug, confirm no amp draw on common, start or run wires.
  6. At the control board ECM terminal, confirm about 12VDC between G and C.
  7. At the blower high voltage connector, confirm amp draw on T1 and T2.
  8. Do not unplug the blower motor while it is running.

Applies to: Vitocal 100-WA with R-454B refrigerant

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 48. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.