Viessmann · Heat pump troubleshooting

Wind, snow and rain protection

Vitocal 100-AW AM2V

What is going on

Check loads and protect the unit when the site is exposed.

Check in this order

  1. In wind-exposed areas, check wind loads, especially on a flat roof, using local wind zone and building height.
  2. Include the outdoor unit in the lightning protection system.
  3. In snowfall areas, mount on a snow stand or wall bracket high enough above the expected snow load.
  4. When designing a rain canopy, allow for heat input in heating mode and heat output in cooling mode.
  5. Confirm the stand or bracket is rated for the unit weight (see Outdoor Unit Technical Data, p. 109).

Applies to: Exposed or snowy sites

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-AW AM2V Installation, Service and Operating Instructions, p. 37-40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.