Weil-McLain · Heat pump troubleshooting

Water chemistry and Sentinel X100 inhibitor

ECO HP

What is going on

Sentinel X100 is required for the ECO HP to protect its heat exchanger. Check water chemistry after filling.

Likely causes

  • Water outside pH 7.0-8.5 or with too little inhibitor can cause corrosion.
  • Chloride above 100 ppm is not allowed in the heat pump.

Check in this order

  1. Fill the system, then add X100 aerosol as the container directs.
  2. Let the water circulate, then check the inhibitor level with the Sentinel test kit. Add more if needed.
  3. Test the water pH at least once a year. It must be between 7.0 and 8.5.
  4. If pH is out of range, consult a local water treatment company.
  5. Verify chloride is below 100 ppm before filling.
  6. Do not use the heat pump to heat swimming pool or spa water.
  7. Check antifreeze concentration at least once a year if antifreeze is used.

Applies to: ECO HP split air-to-water heat pump

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO HP Heat Pump Application Guide, pp. 60-61. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.