Water chemistry and Sentinel X100 inhibitor
What is going on
Sentinel X100 is required for the ECO HP to protect its heat exchanger. Check water chemistry after filling.
Likely causes
- Water outside pH 7.0-8.5 or with too little inhibitor can cause corrosion.
- Chloride above 100 ppm is not allowed in the heat pump.
Check in this order
- Fill the system, then add X100 aerosol as the container directs.
- Let the water circulate, then check the inhibitor level with the Sentinel test kit. Add more if needed.
- Test the water pH at least once a year. It must be between 7.0 and 8.5.
- If pH is out of range, consult a local water treatment company.
- Verify chloride is below 100 ppm before filling.
- Do not use the heat pump to heat swimming pool or spa water.
- Check antifreeze concentration at least once a year if antifreeze is used.
Applies to: ECO HP split air-to-water heat pump
More heat pump guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO HP Heat Pump Application Guide, pp. 60-61. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.