Application B2 piping layout
What is going on
Primary/secondary piping for two space heating zones and a DHW zone, with a boiler circulator and heat pump circulator in the manifold.
Check in this order
- Set up the easy-up or field-fabricated manifold for the heat pump and boiler.
- Install the boiler circulator (shipped loose with the boiler) on the boiler piping.
- Install the heat pump circulator (in the heat pump manifold) with its internal flow check valve.
- Install relief valves on the boiler and heat pump and pipe them to drain.
- Install isolation valves, Y-strainer with 80 mesh screen, expansion tank, air separator and purge/drain valves.
- Install zone valves and zone circulators, and the DHW circulator with DHW temperature and pressure relief valve.
- Keep piping within the spacing shown (do not exceed 8 pipe diameters apart).
- Install unions where needed for service and add a make-up water supply.
Applies to: System Type B, Application B2
More heat pump guides
- Application A1: multi-zone space heating with DHW as zone
- Application B1 heat pump indoor unit wiring
- Application B1 thermostat interface unit (TIU) wiring
- Application B2 heat pump indoor unit wiring
- Application C1 wiring (120 Vac input and TIU priority end switch)
- Application C2 circulators and primary/secondary piping
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO HP Heat Pump Application Guide, p. 31. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.