Weil-McLain · Heat pump troubleshooting

Application C2 circulators and primary/secondary piping

ECO HP

What is going on

Multi-zone space heating with zone valves. Piping must be primary/secondary. The heat pump circulator sits in the heat pump manifold.

Check in this order

  1. Pipe the system as primary/secondary.
  2. Size the system circulator for the required head.
  3. Check the system circulator current draw.
  4. If the system circulator draws more than 0.2A, install an isolation relay.
  5. Confirm the heat pump circulator is installed in the heat pump manifold (included in the heat pump accessory box).

Applies to: Application C2 multi-zone space heating

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO HP Heat Pump Application Guide, p. 50. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.