Verify thermostat circuits (external wiring check)

ECO HP

What is going on

Confirm no voltage is fed back into the boiler control module from external devices.

Likely causes

  • Voltage feeding back from external wiring can damage the control module.
  • Connecting thermostat terminals to 3-wire zone valves can damage the control.

Check in this order

  1. Mark the wires on the thermostat inputs of the control board (Unity 2.0 board for Type A, DHW-priority zone panel for Types B and C).
  2. Disconnect the external thermostat circuit wires.
  3. Close each thermostat, zone valve or relay one at a time. Measure voltage from each wire to ground.
  4. There should never be a voltage reading when an external device is closed.
  5. If voltage is found, correct the external wiring.
  6. Do not connect thermostat terminals to 3-wire zone valves.
  7. Reconnect the thermostat wires after the check.

Applies to: ECO HP with boiler and thermostat inputs

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO HP Heat Pump Application Guide, p. 61. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.