Weil-McLain · Heat pump troubleshooting
Verify thermostat circuits (external wiring check)
What is going on
Confirm no voltage is fed back into the boiler control module from external devices.
Likely causes
- Voltage feeding back from external wiring can damage the control module.
- Connecting thermostat terminals to 3-wire zone valves can damage the control.
Check in this order
- Mark the wires on the thermostat inputs of the control board (Unity 2.0 board for Type A, DHW-priority zone panel for Types B and C).
- Disconnect the external thermostat circuit wires.
- Close each thermostat, zone valve or relay one at a time. Measure voltage from each wire to ground.
- There should never be a voltage reading when an external device is closed.
- If voltage is found, correct the external wiring.
- Do not connect thermostat terminals to 3-wire zone valves.
- Reconnect the thermostat wires after the check.
Applies to: ECO HP with boiler and thermostat inputs
More heat pump guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO HP Heat Pump Application Guide, p. 61. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.