Viessmann · Heat pump troubleshooting

Verify refrigerant leak mitigation (GAS fault)

Vitocal 100-WA

What is going on

When the A2L sensor detects leaked refrigerant, the compressor is shut off and the blower runs continuously. The display flashes GAS until power is cycled. Use this check to confirm the mitigation is working.

Likely causes

  • A2L refrigerant leak sensor detected leaked refrigerant.

Check in this order

  1. Confirm GAS fault is shown on the information display.
  2. On Screen 1, confirm LFL% is above 15%.
  3. Confirm compressor percentage is 0.
  4. Confirm fan % is above 10%.
  5. At the control board, confirm C1 and C2 outputs are not supplying 24VAC to the compressor start relay.
  6. At the start relay, confirm the 24VAC coil side and 230V load side are not energized.
  7. At the compressor molded plug, confirm there is no amp draw on the common, start or run wire.
  8. At the control board ECM terminal, confirm 12VDC ±0.5V between G and C.
  9. At the blower high voltage connector, confirm amp draw on T1 and T2 while the blower runs. Do not unplug the motor while it is running.

Applies to: Ducted installations using the blower for leak mitigation

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-WA installation, service and operating instructions, p. 48. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.