Weil-McLain · Heat pump troubleshooting
Verify heating operation (System Type A)
What is going on
Test the heat pump and boiler with a thermostat call.
Likely causes
- Outdoor temperature or target temperature is outside the application limits, so the heat pump will not run.
Check in this order
- Make a thermostat call. The ECO HP should run and begin heating.
- If the heat pump does not run, check that outdoor or target temperature is inside the application limits.
- To test temporarily, adjust the AHD settings, then return them to application settings before finishing commissioning.
- To check the boiler first, disable AHD temporarily. Follow the boiler manual startup checks.
- Re-enable AHD before finishing commissioning.
Applies to: ECO HP System Type A
More heat pump guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO HP Heat Pump Application Guide, p. 61. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.