Verify heating and DHW operation (System Types B and C)
What is going on
Test each zone and DHW call with the thermostat or DHW input.
Likely causes
- Outdoor temperature is outside the T4HMAX/T4HMIN limits, so the heat pump will not run.
Check in this order
- Make a thermostat call. The ECO HP should run and begin heating.
- If it does not run, check that outdoor temperature is inside the limits. Temporarily adjust T4HMAX and T4HMIN to test, then restore application settings.
- For System Type B, the SG terminals on the HP IDU control board can force AHS calls. No thermostat or DHW call can do this. Close the contacts and the boiler should receive a call for heat.
- Refer to the boiler manual for startup checks.
- Repeat the tests for each zone or DHW call.
Applies to: ECO HP System Types B and C
More heat pump guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO HP Heat Pump Application Guide, pp. 62. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.