Weil-McLain · Heat pump troubleshooting

Verify flow rate through the ECO HP

ECO HP

What is going on

Confirm the heat pump has enough flow before running it. It will not operate below 3.1 GPM.

Likely causes

  • Closed or partly closed zones reduce flow below the minimum.
  • A strainer that is plugged or air in the system reduces flow.

Check in this order

  1. Find which space heating loops can be closed by mechanical, electronic or other valves.
  2. Close all space heating loops that can be closed.
  3. Start the circulation pump. Use the Test run menu and Point check menu in the For Serviceman menu to run Pump_i manually.
  4. Read the flow and adjust until it is between 6 and 10 GPM.
  5. With the Easy-Up Manifold, set the circulator speed dial to MAX for about 7-12 GPM, then use ECOCalc to fine-tune.

Applies to: ECO HP split air-to-water heat pump

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO HP Heat Pump Application Guide, p. 61. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.