Weil-McLain · Heat pump troubleshooting

Unit on but not heating or cooling as expected

Weil-McLain ECO HP

What is going on

Unit runs but the water temperature does not get where it should.

Likely causes

  • Temperature limits set wrong
  • Water flow too low
  • Too little water in the system

Check in this order

  1. Check the T4 limit parameters for the mode: T4HMAX/T4HMIN (heat), T4CMAX/T4CMIN (cool), T4DHWMAX/T4DHWMIN (DHW).
  2. Check every shut-off valve is open and the strainer is clean.
  3. Purge air. Check the gauge: cold water pressure must be over 14.5 psi.
  4. Check the expansion tank and that the pipe system is not too restrictive for the pump.
  5. Confirm system water volume is above the minimum (manual section 8.5.2).

Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.2 General symptoms, p.53. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.