Unit on but not heating or cooling as expected
What is going on
Unit runs but the water temperature does not get where it should.
Likely causes
- Temperature limits set wrong
- Water flow too low
- Too little water in the system
Check in this order
- Check the T4 limit parameters for the mode: T4HMAX/T4HMIN (heat), T4CMAX/T4CMIN (cool), T4DHWMAX/T4DHWMIN (DHW).
- Check every shut-off valve is open and the strainer is clean.
- Purge air. Check the gauge: cold water pressure must be over 14.5 psi.
- Check the expansion tank and that the pipe system is not too restrictive for the pump.
- Confirm system water volume is above the minimum (manual section 8.5.2).
Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)
More heat pump guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.2 General symptoms, p.53. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.