Weil-McLain · Heat pump troubleshooting

Blank display at first start-up

Weil-McLain ECO HP

What is going on

Nothing shows on the user interface on a new install.

Likely causes

  • Wiring missing or wrong between power supply and unit, or unit and user interface
  • PCB fuse blown
  • E8/E0 at start-up: air in the system or water level too low
  • E2 at start-up: user interface wiring

Check in this order

  1. Turn off power at the disconnect before opening the unit or touching any wiring.
  2. Check power wiring to the unit and the wire to the user interface.
  3. Check the PCB fuse.
  4. E8 or E0 on start-up purge air and fill the system to the minimum level.
  5. E2 check the wiring between the user interface and the unit.

Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO HP IDU Product Manual 550-100-586/0824, Failure diagnosis at first installation, p.42. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.