Pressure relief valve opens

Weil-McLain ECO HP

What is going on

Relief valve lifts and dumps water.

Likely causes

  • Expansion tank failed
  • System fill pressure over 43.5 psi

Check in this order

  1. Replace the expansion tank if it has failed.
  2. Set fill pressure to about 12-15 psi (manual section 8.5.2).

Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.2 General symptoms, p.54. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.