Pump noisy (cavitation)
What is going on
Pump makes a gravel-like noise.
Likely causes
- Air in the system
- Pump inlet pressure too low
Check in this order
- Purge air.
- Check the gauge cold water pressure must be over 14.5 psi, and the gauge itself must work.
- Check the expansion tank and its pre-charge (manual section 8.5.2).
Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)
More heat pump guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.2 General symptoms, p.54. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.