Viessmann · Heat pump troubleshooting
Troubleshooting approach with the LED display
What is going on
Start by checking the indoor unit code, then use the flow charts. Some problems have no code.
Check in this order
- Check the diagnostic code on the indoor unit first; the outdoor board LED shows only a few errors.
- If there is no code, use the diagnostic flow charts for the symptom.
- Disconnect main power before removing covers or boards.
- Power up again to measure the outdoor board inputs and outputs with a digital multimeter.
- Use the wiring diagrams for the measurement points.
- Some DC signals are pulsing; a pulse should move steadily when the signal is present.
- Disconnect main power before reinstalling any board.
Applies to: DLCLRC indoor and outdoor units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-S DLCLRC service instructions, p. 15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.