Viessmann · Heat pump troubleshooting

Triple evacuation method

Vitocal 100-S

What is going on

Repeated pull-down and dry nitrogen purge sequence used to remove moisture and contaminants from the system.

Check in this order

  1. Pump the system down to 500 microns and keep the pump running for an additional 15 minutes.
  2. Close the service valves and shut off the vacuum pump.
  3. Connect a nitrogen cylinder and regulator. Open until system pressure reads 2 psig.
  4. Close the service valve and let the system stand for 10 minutes so dry nitrogen can absorb moisture.
  5. Repeat the evacuation and purge cycle as shown in Fig. 16 until the system holds a deep vacuum.

Applies to: DLCURA outdoor units

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLCURA Service Manual, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.