Weil-McLain · Heat pump troubleshooting

System Type C control connections (ECO HP solo)

ECO HP

What is going on

Type C uses only the ECO HP with no other heat source. Calls for heat or DHW go through a DHW-priority zone panel such as the TIU, and its end switches feed the heat pump inputs. The heat pump only connects directly to dry contacts rated 12 Vdc. Only one zone circulator is supported natively.

Check in this order

  1. Route the heat or DHW call through the TIU end switches to the heat pump inputs.
  2. Use only 12 Vdc rated dry contacts for direct connections to the heat pump.
  3. If priority of circulators or zone valves is needed, use a DHW-priority zone panel with priority functionality, such as the TIU.
  4. Let the heat pump run its own circulator; it can also control one space heat zone circulator.
  5. For a DHW circulator, add an isolation relay.
  6. Use the TIU to control any additional circulators.
  7. Zone valve systems can be wired from the valve dry contacts straight to the indoor unit, unless priority zone valve control is needed.

Applies to: System Type C, ECO HP solo and Multi-HP

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO HP Heat Pump - Application Guide, p. 42. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.