Weil-McLain · Heat pump troubleshooting
System Type B: WM heat pump as master, any boiler as shadow – control overview
What is going on
In System Type B the ECO HP is the master. It decides when the heat pump and the boiler run. The call for heat or DHW goes through a DHW-priority zone panel such as the Weil-McLain Thermostat Interface Unit (TIU), which passes it to the heat pump inputs. The ECO HP can only connect directly to dry contacts rated 12 Vdc. The boiler gets its call when the heat pump AHS dry contacts close. The ECO HP runs its own circulator and can run one space heat zone circulator. Extra circulators need a DHW-priority zone panel with priority functionality. A DHW circulator can be run by the ECO HP with an isolated relay. Zone valve systems can be wired to the indoor unit directly, but priority valve control needs a TIU or equivalent.
Check in this order
- Wire the zone panel or TIU call inputs to the ECO HP dry contacts rated 12 Vdc.
- Wire the ECO HP AHS output contacts to the boiler thermostat input.
- Connect the boiler temperature sensor as specified in the boiler manual.
- Connect the ECO HP-controlled space heat zone circulator.
- Use a DHW-priority zone panel with priority functionality if priority control of circulators or zone valves is required.
- For zone valve systems wired direct to the indoor unit, add priority control devices if priority valve operation is needed.
Applies to: System Type B, ECO HP master with boiler shadow
More heat pump guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO HP Heat Pump – Application Guide, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.