Weil-McLain · Heat pump troubleshooting

System Type B, Application B2 design requirements

ECO HP

What is going on

Primary/secondary multi-zone layout with two space heating zones and one DHW zone, controlled through the DHW-priority zone panel. The boiler has one priority and reset curve because the AHS is a single output.

Check in this order

  1. Pipe the system primary/secondary.
  2. Place the boiler downstream of the heat pump so high return temperatures do not shut the heat pump down when both run together.
  3. Size the zone circulators for the required flow.
  4. Provide space heating and DHW zone circulators (installer supplied). Add more zone panels for additional zones.
  5. Note that the boiler circulator ships loose and the heat pump circulator is installed in the heat pump manifold.
  6. Make sure all zones run safely at supply temperatures up to 149°F, or add mixing valves.
  7. If boiler reset is used, check that the DHW supply temperature curve is sufficient for DHW operation, or use a single boiler target temperature instead (confirm with ECOCalc).
  8. Set the boiler and heat pump controls using the boiler manual and heat pump page 11 navigation.

Applies to: System Type B, Application B2 (primary/secondary)

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO HP Heat Pump Application Guide, p. 30. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.