System Type B, Application B1 piping layout
What is going on
Boiler direct piped with an indirect DHW heater, multi-zone space heating and DHW as a zone. Heat pump, boiler, manifold and zone parts are shown in the piping figure. Items marked as supplied with the boiler or heat pump come with the unit. All others are supplied by the installer.
Check in this order
- Set up the easy-up or field-fabricated manifold for the heat pump and boiler.
- Install a relief valve on the boiler and on the heat pump and pipe each relief valve to drain.
- Fit isolation valves, a Y-strainer with 80 mesh screen, and an expansion tank.
- Install an air separator and purge/drain valves at the points shown.
- Install flow/check or spring check valves and a heat trap where the figure shows them.
- Pipe the DHW circulator, DHW temperature and pressure relief valve, and the indirect water heater if used.
- Pipe zone circulators and zone valves, and fit a bypass pressure regulator.
- Keep piping within the spacing shown in the figure (do not exceed 8 pipe diameters apart).
- Install unions where needed for service and add a make-up water supply.
Applies to: System Type B, Application B1 (boiler direct piped, DHW as zone)
More heat pump guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO HP Heat Pump Application Guide, p. 25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.