Weil-McLain · Heat pump troubleshooting

System Type A: Unity 2.0 boiler as master, ECO HP as shadow

ECO HP

What is going on

The boiler decides when the heat pump and boiler run. Up to 4 zones are supported, depending on system requirements and the boiler's field wiring limits. Extra zones need a DHW-priority zone panel such as the Thermostat Interface Unit. Zone calls go to the boiler inputs. The heat pump runs when the boiler's AHD contacts close and are wired to the heat pump thermostat input. DHW calls come through the boiler's second AHD contact. The heat pump controls its own circulator; the boiler or zone board controls all other circulators. Combi boilers may not suit the master role because input/output pairs 1 and 4 are used for 3-way valve operation.

Check in this order

  1. Wire the boiler's AHD1 contact to the heat pump thermostat input.
  2. Wire the boiler's AHD2 contact for DHW calls.
  3. Connect zone thermostat calls to the boiler inputs; use a zone panel for zones beyond the boiler's inputs.
  4. Check whether a Combi boiler is the intended master, since outputs 1 and 4 may be used for 3-way valve operation.

Applies to: System Type A

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO HP Heat Pump – Application Guide, p. 15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.