Weil-McLain · Heat pump troubleshooting

System Type A, Application A1: multi-zone heating with DHW as a zone – piping layout

ECO HP

What is going on

Primary/secondary piping is required. With a Unity 2.0 boiler, the boiler must sit downstream of the ECO HP so that high boiler water temperatures do not reach the heat pump inlet. The DHW zone is fed through an indirect tank and needs a circulator sized for the tank and piping pressure drop. Large indirect tanks may need different piping for the required flow. Zone circulators must be sized for flow and are supplied by the installer. The heat pump circulator is in the heat pump manifold. ECO Tec boilers have an internal boiler circulator.

Check in this order

  1. Pipe the system primary/secondary.
  2. Place the boiler downstream of the ECO HP when both run together.
  3. Size the DHW circulator for the indirect tank and piping pressure drop.
  4. Size each space heating zone circulator for its zone flow.
  5. Confirm the heat pump circulator is installed in the heat pump manifold.
  6. Use a DHW-priority zone panel such as the Weil-McLain Thermostat Interface Unit if alternate wiring is needed.

Applies to: System Type A, Application A1 (Unity 2.0 boiler with ECO HP)

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO HP Heat Pump – Application Guide, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.