Viessmann · Heat pump troubleshooting
Support and connect heating water piping
What is going on
Piping must be hung on its own supports and must never rest on or be carried by the indoor unit. Fittings are field supplied.
Check in this order
- Flush the heating system thoroughly, especially before connecting the heat pump to an existing system.
- Use an approved pipe sealant or Teflon tape on installation fittings. Apply only a moderate amount of dope and leave 2 threads bare.
- Tighten fittings with the two-wrench method: one wrench holds the indoor unit connector, the second tightens the fitting.
- Install isolation valves so system components can be isolated.
- Keep the pipes within the maximum allowable working pressure of 30 psig (2 bar).
- Keep uninsulated hot water pipes at least 2 in. (50 mm) from combustible components, unless the pipes are suitably insulated.
- If no DHW tank is connected, cap the DHW tank supply connection.
- Check all water side connections for leaks after commissioning and after maintenance.
Applies to: Heating water and DHW connections, indoor unit
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocal 100-AW AM2V installation manual, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.