Strip heater fan enable (F-F) wiring
What is going on
The F-F pair is the fan enable relay coil and is how the heater proves air movement. The elements cannot energize on a heat call unless 24 VAC is also present across F-F. The relay only proves the blower was called, not the airflow.
Likely causes
- No 24 VAC across F-F when the blower is called, so elements will not energize
Check in this order
- Land one F on the thermostat G terminal at the control board; the G terminal carries 24 VAC only while the blower is called.
- Share the G screw with the thermostat G lead, since there is no spare G terminal.
- Land the second F on control common, using a jumper from terminal C at the heater.
- Run the third conductor in the same cable as the AUX pair.
Applies to: Optional electric strip heat accessory
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-WA installation, service and operating instructions, p. 37. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.