Strip heat start-up and commissioning checks
What is going on
Verify the installation before leaving the site.
Check in this order
- Confirm the heater branch circuit is separate from the heat pump supply and fused per the heater data plate.
- Confirm the heater is side mounted and at the required distances.
- Verify AUX polarity B to heater terminal 1, W to heater terminal C.
- Verify fan interlock wiring and confirm 24 VAC across F-F whenever the blower is called.
- Run the blower on high speed and verify airflow meets or exceeds the heater minimum.
- Verify the inlet air temperature at the heater does not exceed 100°F (38°C).
- Put the thermostat in emergency/auxiliary heat and verify the AUX output energizes and the contactor pulls in.
- Observe at least one complete heating cycle to confirm normal heater and safety limit operation.
- Record the heater model number, kW rating and job number in the maintenance record.
Applies to: Optional electric strip heat accessory
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-WA installation, service and operating instructions, p. 38. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.