Service checks for installations using flammable refrigerant
What is going on
Checks to carry out on installations with flammable refrigerant.
Check in this order
- Confirm the actual refrigerant charge suits the size of the room where refrigerant-containing parts are installed.
- Confirm ventilation machinery and outlets work properly and are not blocked.
- If an indirect refrigerating circuit is used, check the secondary circuit for refrigerant.
- Confirm equipment markings are still visible and legible. Correct any illegible markings and signs.
- Confirm refrigerant pipes and components are not exposed to substances that could corrode them, unless they are corrosion-resistant or protected.
- Check that cabling will not be exposed to wear, corrosion, excessive pressure, vibration, sharp edges or other adverse conditions, including ageing and vibration from compressors or fans.
Applies to: Vitocal 100-WA installations with R-454B
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 57. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.