Viessmann · Heat pump troubleshooting

S communication DC voltage check (indoor to outdoor link)

Vitocal 100-S

What is going on

Used when the indoor and outdoor units do not communicate. Measure DC voltage between the S terminal and the N or L2 terminal. The reading shows whether the signal and board are working.

Likely causes

  • Wiring fault between indoor and outdoor units
  • Short-circuited component on the main board
  • Faulty IPM board or main PCB
  • Faulty electronic expansion valve coil

Check in this order

  1. Power off, then restart the unit after 2 minutes.
  2. Measure DC voltage between N or L2 and S. Black probe to S, red probe to N or L2.
  3. If the reading is fixed and close to 0, the indoor unit is faulty.
  4. If the reading alternates between negative and positive, the link is working normally.
  5. If the reading is always positive, the outdoor unit is faulty.
  6. Check the wiring between indoor and outdoor units, and the wiring from the outdoor terminal to the outdoor PCB.
  7. Check the wiring from the indoor terminal to the indoor PCB.
  8. Turn the unit on and check whether W and 1(L) are connected. Check whether the power LED is on.
  9. Check the AC voltage of L and N output to the IPM board. It should match the power input.
  10. Check DC 5 V and 12 V from the IPM board to the main PCB.
  11. Unplug high voltage components on the main PCB one at a time (4-way valve, heater, AC fan) and check their resistance for a short circuit.
  12. Unplug the electronic expansion valve and check the DC 5 V and 12 V again.
  13. Replace any short-circuited component and the main PCB, or replace the IPM board, or replace the indoor PCB, as the checks indicate.
  14. If the expansion valve coil is faulty, replace the coil.
  15. Note: On some models the outdoor PCB cannot be removed separately. In that case replace the whole outdoor electric control box.

Applies to: DLCLRC outdoor units with indoor fan coil

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLCLRC Service Manual, p. 20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.